Can't stop fan from running along Honeywell Thermostadt
We bought a house with a Honeywell thermostadt, and the rooter keeps coming on without explanation (at least as I can figure out). We have tried setting the fan to "auto", yet it will placid come in on at times when the AC is not running. We have even tried turning the system "off" and all the same the fan bequeath still progress at times even with the system remove. See attached two pictures which show that both "on" and "auto" are active under the "Fan" drift. When the "on" is lit ahead, we have not found anything that will come through switch off.
The thermostadt has scheduling curb options, and i have washed-out a lot of time trying to take in if perchance the fan is scheduled to come through on but I don't think this is the case. As noted in the pictures, I have switched the thermostadt to "permanent hold" so the programing is non applicable, but silent cannot stop the fan from coming on.
When the rooter is running and the "on" is lit finished subordinate the "Fan" heading, the only thing I have been competent to do to stop it is to flip the breaker and withdraw complete superpowe to the air handler.
Any advice would live welcome. Thanks
-
what other is the thermoregulator connected to? heaps of other things will cause the sports fan to crook off and on.
-
I believe this will require a tech to go into the frame-up program.
[Avatar photo from a Florida training chance event. Everyone walked away.]
2 Tim 3:16-17RSES CMS, HVAC Electrical Specialist
Member, IAEIAOP Assembly Rules:
-
Post Likes - 1 Likes, 0 Dislikes
-
Nobelium, it's in the temperature programming. For each one clock period stool receive a choice of auto, circ and on rooter. The homeowner only of necessity to enter upon the scheduling and take every period of time for one not set at car.
-
I thought atomic number 2 said that he'd already looked at scheduling....
[Avatar photo from a Florida training chance event. Everyone walked away.]
2 Tim 3:16-17RSES CMS, HVAC Electrical Specialist
Member, IAEIAOP Forum Rules:
-
Do you rich person the manual for the thermostat? If not, you can find information technology online. Check each regular geological period to make sure it is not set for fan connected. Some Honeywell thermostats have a "circ" mode to run the devotee occassionally between cycles.
PS there is no D in thermoregulator.
*********
https://www.hvac20.com/ High efficiency equipment alone does not bring home the bacon home comfort and efficiency. HVAC2.0 is a process for finding the real needs of the house and the occupants. Offer the customer a menu of work to address their problems and give them a probability of success.Find contractors with specific training in combustion analytic thinking, act system performance, beam flow, and duct optimisation
https://www.myhomecomfort.org/
Site phallus map HERE!
-
Since it says ON and AUTO some, tranquillize say to check scheduling.
-
The vision pro will tell auto when not calling, and will add ON when the telephone call starts.
He should probably download the hand-operated atomic number 3 mentioned above, and make sure each daily schedule says "car".
[Embodiment exposure from a Florida training accident. Everyone walked away.]
2 Tim 3:16-17RSES CMS, HVAC Electrical Specialist
Member, IAEIAOP Forum Rules:
-
Mightiness even be some add on fresh air intake system for ventilation. They were Oregon may yet exist required in our res publica.
UA Local 32 retired as of Jan 2022
-
If you took the T/S off the wall does the fan stay spouting????
-
Thanks to all for the responses. As many suspected, it was the scheduling. I turned all of the scheduling options to "auto" which resolved the job. I had thought that when I turned the temp scope to "standing prevail" that it bypassed the programing, but the programming was still turning the fan on. Thanks again.